Phase plane fuzzy identification of the most unfavorable thermal loop in fan-coil unit systems
To realize the optimal control of variable pressure difference in fan-coil unit systems
a phase plane fuzzy identification method was proposed and verified
which takes the terminal branch pressure difference of the most unfavorable thermal loop as the control variable. For fan-coil variable flow air conditioning water system
based on the heat balance equation of air conditioning room
the mathematical relations among the terminal energy difference between supply and demand
the deviation (e) between room temperature and its setpoint
and the deviation change (ec) were established. The most unfavorable thermal loop is defined as the one with the largest terminal energy difference. In the phase plane composed of e and ec
the terminal energy difference of the phase plane could be reflected by the trajectory characteristics of the phase plane connected by phase points S(e
ec). According to the fuzzy pattern recognition process
by taking the real-time tracer direction vector angle (βi) and the room temperature deviation (ei) as characteristic indexes
triangle function as subordinate function
and maximum subordinate degree principle as recognition criterion
the table of fuzzy recognition rules was formulated. The phase plane fuzzy identification method for the most unfavorable thermal loop was then established
and a test platform for variable flow air conditioning water system was built. The water flow of the branches was increased synchronously
and the branches that reached the balance between energy supply and demand are the most unfavorable thermal loops identified by the test. Experimental results show that the proposed method is accurate and reliable
which can be applied to identify the most unfavorable thermal loop in fan-coil unit systems.