ZHAO Xiling, FU Lin, WANG Xiaoyin, et al. Analysis of the recovery system of flue gas from combined heat and power plant with distributed peak-shaving heat pumps[J]. 2018, 50(2): 2018-2.
DOI:
ZHAO Xiling, FU Lin, WANG Xiaoyin, et al. Analysis of the recovery system of flue gas from combined heat and power plant with distributed peak-shaving heat pumps[J]. 2018, 50(2): 2018-2.DOI: 10.11918/j.issn.0367-6234.201607029.
Analysis of the recovery system of flue gas from combined heat and power plant with distributed peak-shaving heat pumps
To improve the natural gas heating supply capacity
distributed heat pump peak-shaving technology has great potential to be further studied and promoted. This technology is to use heat pump to adjust heat on the secondary network in substation
simultaneously
to reduce the return water temperature of primary network by using the principle of heat pump. Return water of primary network with low temperature creates favorable conditions to recover waste heat in heat source
and improve heating efficiency. This paper takes a set of two 9F gas-steam combined cycle back pressure heating unit as an example and evaluates its feasibility and application effect. It is compared with a general gas boiler peak-shaving system on the design and operation condition. For comparison
fuel consumption of these two heating systems are almost the same. Heating energy consumption of new system is reduced by 6%. Dynamic investment-increment payback period is 3.1 years
meaning that the new system has good economy. The research shows that the system can improve network transmission and distribution capacity
increase heating capacity and reduce heating energy consumption. And it also can ensure the safety of heating.