ZENG Lingjie, GAO Jun, DU Bowen. Optimized sensor layout to detect accidental contaminant released in the ventilation system[J]. 2018, 50(2): 2018-2.
DOI:
ZENG Lingjie, GAO Jun, DU Bowen. Optimized sensor layout to detect accidental contaminant released in the ventilation system[J]. 2018, 50(2): 2018-2.DOI: 10.11918/j.issn.0367-6234.201608017.
Optimized sensor layout to detect accidental contaminant released in the ventilation system
This paper illustrated an optimization method of sensor layout in air duct system
aiming at detecting toxicant before any catastrophic consequence in a bio-terrorist attack. The method was based on genetic algorithm (GA) with minimal emissions as objective function of the optimization procedure. In this paper
we discussed the impact of the number of sensors
the distance between nodes and the accuracy of sensors on the optimizing objective function. Results of a case study showed that the minimal emission of contaminants decreased significantly as more sensors were set in the ventilation system. However
the decrement provided by every sensor was only about 2% when the number of sensors exceeded three. Thus
the optimized number of sensors in this case was supposed to be three
considering the high cost of each sensor. Moreover
the value of the objective function was reduced by 59.3% with sensor layout optimization applied with three sensors while the effects of the accuracy of sensors and the distance between nodes were not significant. In conclusion
adopting the sensor layout optimized with GA ensured the detection of contaminants with the minimal distribution into rooms
which enabled a security control center to learn the concentration and location of the contaminants and respond quickly.