LIU Faqi, JILI Amu, YANG Dongdong, et al. Fire performance of circular steel tube confined reinforced concrete columns exposed to natural fire[J]. 2018, 50(12): 38-44.
DOI:
LIU Faqi, JILI Amu, YANG Dongdong, et al. Fire performance of circular steel tube confined reinforced concrete columns exposed to natural fire[J]. 2018, 50(12): 38-44.DOI: 10.11918/j.issn.0367-6234.201801050.
Fire performance of circular steel tube confined reinforced concrete columns exposed to natural fire
主要考察参数为火灾升温速率、升温时间以及构件荷载比.真实火灾的温度-时间关系采用欧洲规范Eurocode 1 Part 1-2建议的参数火灾模型计算
并选取了ISO-834标准火灾作为对比.分析结果表明:真实火灾的升温速率越快、升温时间越短
构件的截面温度梯度越大;真实火灾作用下
圆钢管约束钢筋混凝土柱不仅可能会在升温过程中发生破坏
也可能会在降温过程中发生破坏;基于等效曝火时间的方法
将计算得到的真实火灾下耐火极限转换为标准火灾下的等效耐火极限
当真实火灾升温速率小于标准火灾速率时
采用标准火灾曲线得到的耐火极限比等效耐火极限小;而当真实火灾升温速率大于标准火灾时
采用标准火灾曲线得到的耐火极限比等效耐火极限大
即按标准火灾下进行的设计偏于不安全
建议按照真实火灾进行抗火设计.
Abstract
To investigate the fire performance of circular steel tube confined reinforced concrete (STCRC) columns exposed to natural fire
a finite element model including thermal analysis model and stress analysis model was developed using the software ABAQUS. The main considered parameters were fire heating rate
heating duration time and load ratio. Parametric temperature-time curves recommended by Eurocode 1 were employed as the temperature curves of natural fire
and the ISO-834 standard fire curve was selected as a comparison. The results showed that the faster heating rate and the shorter heating duration time of nature fire resulted in the higher temperature gradient of the composite cross section. Circular STCRC columns exposed to natural fire might fail in the heating phase or the cooling phase. Based on the method of equivalent fire exposure time
the fire resistance under natural fire and standard fire could be converted reciprocally and then compared with each other. It was found that fire safety design with ISO-834 standard fire curve was conservative when the heating rate of natural fire was slower than that of the standard fire. However
fire safety design with ISO-834 standard fire curve was unsafe when the heating rate of natural fire was faster than that of the standard one. Thus
natural fire curve in fire safety design is recommended for this condition.