Film cooling performances of two fan shaped film holes at different positions on blade suction side were experimentally studied in a linear transonic cascade. The film cooling effectiveness of the fan shaped film holes on blade suction side was measured at mainstream inlet Reynolds number of 3.7×105
different mainstream exit Mach number of 0.81
0.91
1.01
and different blowing ratio of 0.6-2.1. Results shows the film hole 2 is at the position with higher curvature
where the mainstream forces the coolant to better flow along the surface
however
this has both advantages and disadvantages. At smaller blowing ratio
the jet of film hole can flow close to the wall itself
so the advantage of the mainstream isnt obvious
but the mainstream forces the coolant to flow downstream and the coolant will be difficult for spanwise flow
bringing about lower film cooling effectiveness. At higher blowing ratio
the jet of film hole has large vertical velocity component
the coolant can be easily lifted off
then coolant of the film hole 2 can be forced to get close to the wall
so the film cooling effectiveness is increased substantially.