Temperature Distribution of Large Scale 4-Pole Turbo-Generator Stator
The newly developed AP1000 water-hydrogen cooled 4 pole turbo-generator stator is the research object
in which cooling structure
cooling mode and cooling performance of cooling medium are analyzed. In order to set up the one to one correspondence with the rotor
1/32 circular structure of 3 dimensional model of the whole stator
rotor and air gap is established
and cooling medium temperature distribution characteristics are analyzed by u- sing the computational fluid mechanics principle. The temperature distribution of the stator iron core
magnetic shielding
pressure plate
copper coils and the location of the maximum temperature of each part are gotten. Maxi- mum temperature rising is calculated
which is within engineering reasonable range. It is the reference for structure design and optimization of ventilation for the turbine generator.