北京工业大学 城市建设学部,北京,100124
纸质出版:2022
移动端阅览
侯本伟, 肖恒圣, 吴珊. 考虑天气因素的给水管道漏损预测模型[J]. 哈尔滨工业大学学报, 2022,54(2):8-16.
HOU Benwei, XIAO Hengsheng, WU Shan. Failure prediction model of water distribution pipelines considering weather factors[J]. 2022, 54(2): 8-16.
侯本伟, 肖恒圣, 吴珊. 考虑天气因素的给水管道漏损预测模型[J]. 哈尔滨工业大学学报, 2022,54(2):8-16. DOI: 10.11918/202012047.
HOU Benwei, XIAO Hengsheng, WU Shan. Failure prediction model of water distribution pipelines considering weather factors[J]. 2022, 54(2): 8-16. DOI: 10.11918/202012047.
天气变化引起土壤含水率变化和变形等
导致气温变化与市政给水管道的破损事件存在相关性。为此
基于北方某城市给水管网破损事件数据和气温记录
分析不同的天气因素量化指标与管道破损事件的相关性。采用误差反向传播神经网络(BPNN)和基因表达式编程(GEP)方法
建立考虑天气因素的给水管道漏损预测模型。根据案例城市过去11年的市政给水管网破损记录数据库、管道地理信息数据库和同期气温记录
分析6个天气因素指标(平均温度、冰冻指标、最大上升值、最大下降值、最大上升率、最大下降率)的内在相关性及其与管道破损事件的相关性;采用BPNN和GEP建立管道破损数(因变量)与4个自变量(代表性天气因素指标、管径、管龄、管长)的隐式和显式函数关系。应用隐式和显式两种模型预测案例城市给水管网未来1年的破损数
未考虑天气因素的模型预测决定系数分别为0.65和0.60
考虑天气因素模型预测结果的决定系数分别为0.78和0.88
预测精度提升率分别为13%和28%。建立考虑天气因素的给水管道漏损预测模型是合理有效的。
Due to the changes in soil moisture content and deformation caused by weather changes
there is a correlation between weather temperature and failures of urban water distribution pipelines. Based on the failure records of pipelines and weather temperatures of a northern China city
the correlations between different weather temperature indicators and water mains failures were analyzed. The failure prediction models of water distribution pipelines considering weather temperature factors were established using error back propagation neural network (BPNN) and genetic expression programming (GEP) methods. According to the failure records of water distribution pipelines
pipeline geographic information
and weather temperature records of the case city in the past 11 years
the correlations among pipeline failures and six weather factors were analyzed
including average temperature
freezing indicator
maximum increase
maximum decrease
maximum increase rate
and maximum decrease rate. BPNN and GEP were used to establish the implicit and explicit relationships between the number of pipeline failures (i.e.
the dependent variable) and four explanatory variables (the selected weather temperature indicator
the diameter
age
and length of pipelines). The explicit and implicit models were used to predict the number of pipeline failures in the case city in the next year. The determination coefficients of the prediction results of the model without considering weather factors were 0.65 and 0.60 respectively
while those considering weather factors were 0.78 and 0.88
where the prediction accuracy increased by 13% and 28%. Therefore
it is reasonable and effective to establish a failure prediction model of water distribution pipelines by considering weather factors.