To explore the vulnerability of different part of a reinforced concrete cooling tower in service
numerical simulation analysis was carried out. The software ABAQUS was selected to establish analysis model. According to the field conditions where the structure locates in
a range of reasonable ground motion records were selected and then incremental dynamic analysis was conducted. Material strain and peak ground acceleration were selected as engineering demand and intensity measure parameters
respectively. The structure was divided into 13 regions in the height direction
and the damage states of the structure were divided into five levels. Unidirectional
bidirectional horizontal and three-dimensional seismic action were respectively exerted to the bottom of the structure
the regression analysis on the structure response was performed. The probabilistic seismic demand model of the structure was established
and the partitioned vulnerability curves of different parts were obtained. The analysis results show that: the damage probability of the upper tower is relatively small and the herringbone pillars' damage probability is significantly higher than the other parts of the structure. The herringbone pillars at the bottom are the most injury-prone part
which can be reinforced according to the actual needs