Based on the gas molar flow rate at fuel tank outlet
the molar flow relationship between the gas components flowing through the catalytic reactor and the cooler was deduced
and a mathematical model of the oxygen-consuming inerting system was established. The effect of ambient temperature on “water” performance in the system was studied. Results showed: as the inerting developed
the proportion of water vapor on fuel tank ullage gradually increased
while the amount of cooling air
the relative humidity at the reactor outlet and the amount of removed water decreased. The impact of liquid water precipitation on cooling air amount was huge and cannot be ignored. In addition
the generation and precipitation of water in the system were related to the ambient temperature. The lower ambient temperature indicated the slower rise of water vapor volume on fuel tank ullage
but more cooling air required by the system and the greater amount of precipitating liquid water. For example
when the ambient temperature was 0 ℃
the amount of cooling gas required in the cooler was about 111 times and 126 times of that at 20 ℃ and 40 ℃
respectively.Therefore
when designing an oxygen-consuming inerting system
the effect of temperature changes on the generation and precipitation of water should be fully considered.