叶振起, 魏来, 林茂盛. 余热锅炉型联合系统调试临时电源控制器建模及稳压分析[J]. 机械科学与技术, 2025,44(9):1622-1627.
叶振起, 魏来, 林茂盛. Modeling and Voltage Regulation Analysis of Temporary Power Controller for Waste Heat Boiler Type Combined System Commissioning[J]. Mechanical Science and Technology for Aerospace Engineering, 2025, 44(9): 1622-1627.
叶振起, 魏来, 林茂盛. 余热锅炉型联合系统调试临时电源控制器建模及稳压分析[J]. 机械科学与技术, 2025,44(9):1622-1627. DOI: 10.13433/j.cnki.1003-8728.20230238.
叶振起, 魏来, 林茂盛. Modeling and Voltage Regulation Analysis of Temporary Power Controller for Waste Heat Boiler Type Combined System Commissioning[J]. Mechanical Science and Technology for Aerospace Engineering, 2025, 44(9): 1622-1627. DOI: 10.13433/j.cnki.1003-8728.20230238.
余热锅炉型联合循环系统电源电压控制过程受到串联、并联交流器影响,电源电压控制失稳,提出基于有限控制集模型预测控制(Finite control set model predictive control
FCS-MPC)的余热锅炉型联合循环系统电源控制方法。构建由串联变流器与并联变流器共同构成电源控制器拓扑结构;采用FCS-MPC方法,构建电源控制器离散化数学模型,以开关时间和全局控制误差为约束条件,约束控制量和判断角度,将控制模型转换为约束优化问题,判断未来某时刻控制器状态量;设置控制器状态量参考值,设计价值函数分析不同开关状态的判断结果,并在变流器内输入最优开关状态,完成控制器稳压控制。测试结果显示,该方法可提升余热锅炉型联合循环系统电源控制器电压利用率与电压稳定性。
The power supply voltage control process of the combined cycle system of waste heat boiler is affected by series and parallel alternators
and the power supply voltage control is unstable. A power supply control method of waste heat boiler combined cycle system based on FCS-MPC (Finite control set model predictive control) is proposed. The topology of power controller is constructed by series converter and parallel converter. By using FCS-MPC method
the discrete mathematical model of power controller is constructed. Taking the switching time and global control error as the constraints
the control quantity and judgment angle are constrained. The control model is transformed into a constrained optimization problem to judge the controller state quantity at a certain time in the future. By setting the reference value of the controller state quantity
designing the value function
analyzing the judgment results of different switching states
and inputting the optimal switching state in the converter to complete the voltage stabilizing control of the controller
the results show that the present method can improve the voltage utilization and voltage stability of the power controller of the waste heat boiler combined cycle system.