杨迁, 韩利平, 冯琛琛. Analysis on energy-saving effect of intelligent ventilation system in communication base station[J]. 2015, 28(11): 83-87. DOI: 10.13992/j.cnki.tetas.2015.11.018.
This paper discussed the energy-saving effect of intelligent ventilation system in communication base station with measured data. The results showed that the yearly electricity-saving per unit area of base station with intelligent ventilation system distributed in 60
1
00 k W·h/m2
the electricity-saving rate distributed in 10%
2
5%. Furthermore
the energy-saving effect was more significantly with lower temperature outside and longer time with low temperature. In central and southern Shaanxi
the operation time of air-conditioning shorten 13%
2
0% in communication base station with intelligent ventilation system. While
the value was 20%
2
4% in northern Shanxi. Fina
lly
it provided some proposals about the applicable conditions and management aiming at three thermal types.